DA-V200
Alarm Input Processing for up to 16 Zones
Product Description
The DA-V200 Input Monitor Interface is a 16-input alarm input processor designed? to connect various types of alarm initiating devices such as door contacts, motion sensors and other devices providing dry contact signal for supervision and monitoring. The DA-V200 input monitor interface connects up to 16 supervised input circuits. Each input point monitors and reports normal, off-normal, and alarm states.
A maximum of 16 DA-V200 or mixed with other Delta interface modules may be connected through one channel of high-speed RS-485 communication link to the DA-V1000 Network Controller The network controller provides two RS-485 communication channels. The DA-V200 features on-board flash memory, allowing program updates to be uploaded through the network. The network controller communicates with the system host via industry standard TCP/IP protocol over 10/100 Mbps Ethernet or the Internet. This architecture minimizes the impact on corporate LANs by using only one TCP/IP address for every 32 Delta interface modules.
Key Features
- Reports supervised or un-supervised alarm circuits status
- Off-normal condition programmable for each input point (NO or NC alarm devices may be used)
- Connects to the V1000 via RS-485
- Receives and processes real time commands from the V1000
- Reports all activity to the V1000
- Allows complex input/output linking when used with the V1000 and V300 Output Control Interface
- Attractive polycarbonate enclosure protects components from damage
- All connections and indicators are fully identified by silk-screened nomenclature on the cover
- UL 294 and UL 1076 recognized components
Mounting
- Mount to any wall surface, using four screws. For UL compliance, one or more interfaces can be mounted inside a locking customer supplied NEMA-4 rated enclosure with:
- DC supply with battery back-up
- Enclosure tamper switch
- All connections made through conduit
- The unit should be installed indoors, inside a secure area, such as in an IT or telecommunications room, utility closet, or on a wall above a suspended ceiling.
Visual Indicators
- Communications LED flashes green for “transmit to host” and red for “receive from host.” Power LED indicates that sufficient DC voltage is being provided to the unit.
Easily Interfaced
- Quick-disconnect screw terminal connectors
- Rotary address switch (0-15)
- Inputs for:
- 16 input circuits
- AC Fail Monitor*
- Battery Fail Monitor*
- Enclosure Tamper*
- *Can be configured as a general purpose input
Non-latching relay outputs (rated 2A@30VDC):
- 2 auxiliary devices: alarm host offline (comms down), or general purpose
Local Processing
- Basic input/output linking using inputs 1 and 2, and auxiliary outputs 1 and 2
Dimensions
- 5.8” W x 4.825” H x 1.275” D (147.32 mm x 122.55 mm x 32.38 mm)
Weight
- 12.4 oz (.35 kg)
Specification
Enclosure Material
- UL94 Polycarbonate
Power Supply Requirements
- 50 mA @ 9-18 VDC
- Recommended: Supervised linear power supply with battery back-up, input surge protection, and AC fail and battery low contact outputs.
- Separate supervised DC supply with battery back-up recommended for relay activated devices.
Operating Environment
- Indoors, or customer-supplied NEMA-4 rated enclosure
Temperature
- 32° to 122°F (0° to 50°C)
Humidity
- 5% to 95% relative, non-condensing
Communications Ports
- RS-485 – two wire.
Input Circuit Supervision
- Configurable for EO resistor values of 1K through 10K. Can also be configured for use as unsupervised circuits.
Certifications
- UL 294 and UL 1076 Recognized Component for the US, CSA 205 for Canada, FCC Class A Verification, EMC for Canada, EU (CE Mark), Australia (C-Tick Mark), New Zealand, Japan EN 50130-4 Access Control Systems Immunity for the EU (CE Mark)
Cable Distance
- RS-485 – 4000 feet (1220 m) to host, using Belden 3105A, 22AWG twisted pair, shielded 100Ω cable
- Input Circuits – 500 feet (150 m), two-conductor, shielded, using ALPHA 1292C (22AWG) or Alpha 2421C (18AWG)
- Output Circuits – 500 feet (150 m), 2-conductor, using ALPHA 1172C (22AWG) or Alpha 1897C (18AWG)
- Minimum wire gauge depends on cable length and current requirements.
Delta is committed to its policy of continual product and system improvement. Delta reserves the right, without obligation and without prior notice, to change product specifications and/or engineering design.